Dranetz Visa Betriebsanweisung Seite 46

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 77
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 45
DB-PX5 - PowerVisa 440® / PowerGuide® 4400 / PowerXplorer® PX5 Op. Skills
© 2006-2010 by PowerCET Corporation. All rights reserved. (100616)
45
©2006-2008 PowerCET Corporation. All rights reserved.
89
Press limit field under Volts
or Amps to change limit
This sets the threshold
limit beyond which rms
voltage/current variations
occur
Similar to previous screen
with window set at 100%
Press: Enable
Press Amps to toggle
between volts and amps
Press the other tabs to set
other channels
Press: Next to continue
Wizard Setup: Transient Limits-RMS Distortion Waveshape
©2006-2008 PowerCET Corporation. All rights reserved.
90
Press limit field under
Volts or Amps to change
limit
This chooses the
number of cycles before
and after the trigger
cycle to capture
Press: Use Default to
capture Pre: 1, Post: 2
Press: Set same as RMS
variation to capture Pre: 2,
Post: 2
Press: Finish to complete
Transient Limit setup and
return to will return to the
Advanced Options menu
Wizard Setup: Transient Limits-Pre/Post Cycle capture
Seitenansicht 45
1 2 ... 41 42 43 44 45 46 47 48 49 50 51 ... 76 77

Kommentare zu diesen Handbüchern

Keine Kommentare