B-4
Measured Parameters
Measured Parameters
Voltage
Type: 4 full differential, DC coupled
Channels A, B, C, D Input Range: 10 - 600 Vrms
Input impedance: 16 MΩ, minimum, Input to Input
RMS Accuracy: ±0.1% of Reading, ±0.05% Full Scale, over 7KHz bandwidth
(1 second rms readings)
CMRR: -80 db typical
Current
Type: 4 full differential, DC coupled.
Channels A, B, C, D Input Range: 10 - 200% of Rated Probe Input (Dranetz-BMI
probes)
RMS Accuracy:
±0.1% of Reading ±0.05% Full Scale plus Probe Accuracy, 3KHz bandwidth (1 second
rms readings)
Phase
Each voltage/current pair (i.e. Channel A voltage, Channel A current) are sampled
simultaneously to preserve phase relationship.
Frequency
Two ranges, user selectable.
For PowerVisa:
30 - 70 Hz default, with up to 25% Vthd
15 - 30 Hz
Accuracy: ±0.2% of reading
Environmental
All specifications are met over the operating range with influence factors as per IEC
61000-4-30 Class A.